Large Eddy Simulation (LES) of Tunnel Pool Fire and calculation Infra Red absorption Coefficients of Soot Particles

1. Introduction

Tunnel development is proceeding to reduce transportation time and to achieve efficient use of space. Maintenance and management of these tunnels are now important, due to increased demand for greater use and the needs for construction of tunnels [1]. Therefore, because of increased usability of tunnels, the prevention of fire and emergency evacuation becomes important matters to consider. In particular, when fire occurs in a tunnel, there is a serious possibility of massive injuries to those trapped inside. In addition, substantial property damage is always expected. There were some cases of accidents: the Mont Blanc tunnel fire (1999) in France-Italy; and the Tauern tunnel fire (1999) in Austria, in which there were large numbers of casualties and huge property damage [2].

CFD simulation – fire inside a tunnel

The following video shows the possible effect of high temperatures on a concrete horizontal surface. The spallation of concrete can damage structures and the collapse of structures on vehicles:

The cases above illustrate the reasons why an early-stage detection system is required, to reduce such losses. Therefore, we try to minimize such damage by developing a device that detects fire as early as possible. In this post, a new algorithm has been developed in order to calculate the infrared radiation attenuation by soot particles, Carbon Dioxide, Carbon monoxide and water vapor inside tunnel pool fire. The mechanism of pool fire is described in the following video:

Numerical Simulations of Plume and Pool Fire Instabilities using Adaptive Mesh Refinement

The computational work consists from two phases: FDS software has been implemented in order to calculate the temperature, soot, CO and  concentration fields and then  HITRAN database has been applied in order to calculate the refractive indices of soot particles (n, k) and the absorption parameters of the gaseous species.

2. Computational Fluid Dynamics Model

The Fire Dynamics Simulator (FDS) has been developed at the Building and Fire Research Laboratory (BFRL) at the National Institutes of Standards and Technology (NIST), e.g. McGrattan et al. [3, 4]. The program calculates the temperature, density, pressure, velocity, and chemical composition within each numerical grid cell at each discrete time step. It computes the temperature, heat flux, and mass loss rate of the enclosed solid surfaces. The latter is used in the case where the fire heat release rate is unknown. The following is a brief description of the major components of the model.

Hydrodynamic Model – FDS code is formulated based on Computational Fluid Dynamics (CFD) of fire-driven fluid flow. The FDS numerical solution can be carried out using either a Direct Numerical Simulation (DNS) method or Large Eddy Simulation (LES). The latter is relatively low Reynolds numbers and is not severely limited in grid size and time step as the DNS method. In addition to the classical conservation equations considered in FDS, including mass species momentum and energy, thermodynamics based state equation of a perfect gas is adopted along with chemical combustion reaction for a library of different fuel sources.

Combustion Model – For most applications, FDS uses a mixture fraction combustion model. The mixture fraction is a conserved scalar quantity that is defined as the fraction of gas at a given point in the flow field that originated as fuel. The model assumes that combustion is mixing controlled, and that the reaction of fuel and oxygen is infinitely fast. The mass fractions of all of the major reactants and products can be derived from the mixture fraction by means of “state relations,” empirical expressions arrived at by a combination of simplified analysis and measurement [5].

Radiation Transport – Radiative heat transfer is included in the model via the solution of the radiation transport equation for a non-scattering gray gas. In a limited number of cases, a wide band model can be used in place of the gray gas model. The radiation equation is solved using a technique similar to a finite volume method for convective transport, thus the name given to it is the Finite Volume Method (FVM) [3]. FDS also has a visual post-processing image simulation program named “smoke-view”.

3. HITRAN Database

The HITRAN database project has its origins in compilations of spectral parameters for water vapor and carbon dioxide almost four decades ago[7] and culminated in the first public, machine-readable edition [7] in 1973. HITRAN has evolved from a compilation of parameters for the principal atmospheric absorbers in the infrared to a large database covering the microwave through ultraviolet regions, containing additional parameters for the demands of remote-sensing satellite experiments, and with many molecular constituents. Meanwhile, there has also been great progress in the acquisition of spectral parameters for trace gases, major improvements for the major gases such as water vapor and ozone, and the measurement of cross-section data for the “heavy” gases. HITRAN itself, the line-by-line portion of the compilation, is now part of a much larger ensemble of tools for modeling. First, the compilation includes HITRAN (significantly updated as always) and several other databases for the “matter” part of the modeling of the interaction of matter and radiation. In addition to HITRAN, the compilation has directories containing cross section data of heavier species or molecules with very dense spectral features, UV cross-sections and line-by-line parameters, supplemental files (such as for parameters in HITRAN-like format, but consigned to a subordinate folder because they may be better represented for simulation studies in the cross-section files), aerosol indices of refraction, the accompanying HAWKS software and documentation, and HITEMP, the high-temperature analogous database to HITRAN.

4. Description of CFD Calculations

The dimensions of the tunnel were 20 m long, 7.4 m wide and 5 m high. It was assumed that the Heptane fuel has been burned. 12 thermo-couples have been placed inside the tunnel.  An oxygen concentration detector has been placed at the left corner of the tunnel.  In this work, it was assumed that there isn’t ventilation in the tunnel.  The CFD simulation result will be presented in this section. One advantage of CFD simulation is that it can provide much detailed information on the fire, including the local and transient gas velocity, gas temperature, species concentration, solid wall temperature, composite burning rate, radiation heat transfer, convection heat transfer and Heat Release Rate (HRR).   

5. Results

This section divided into two parts. In section 5.1 FDS results are shown. In section 5.2 the calculation of the soot absorption coefficient is presented.

5.1 Fire Dynamic Simulator (FDS) Results

The CFD simulation result will be presented in this section. One advantage of CFD simulation is that it can provide much detailed information on the fire, including the local and transient gas velocity, gas temperature, species concentration, solid wall temperature, composite burning rate, radiation heat transfer, convection heat transfer and heat release rate (HRR). The temperature field at t=9 s is shown in figure 1.

Figure. 1: Temperature field in the tunnel at t=9 sec.

It can be seen from figure 1 that the ceiling temperature at time=9 sec approaches to 930ºC (The peak temperature results obtained by FDS software (930 °C) has been compared to the literature. It is claimed that typical post-flashover room fire will have more commonly a peak temperature of 900 to 1000 °C (1652 to 1832 °F)- see the following paper: https://www.mdpi.com/2227-9717/8/2/145/htm). The spatial concentration of the soot inside the tunnel is shown in figure 2.

Figure 2: Soot concentration field in the tunnel at t=9 sec.

It can be seen from figure 2 the effect of “back layering”. Back layering (also known as “back-flow”) is the name given to the phenomenon when smoke from a fire is observed to move against the direction of the airflow in the tunnel [10]. The calculated oxygen mole fraction is shown in figure 3.

Figure 3: Calculated oxygen mole fraction

Figure 3 shows that the combustion reaction causes the oxygen concentration to decrease. This is because the oxygen is consumed by the Heptane oxidation reaction.

5.2 Calculation of the soot absorption coefficient

The soot absorption coefficient is calculated according to [11]:

Where:

is the soot density and T is the temperature. The soot density and the temperature are calculated by FDS software. The soot density distribution inside the tunnel as a function of z at t=300 sec and 3000 sec is shown in figure 4.

Figure 4: The Soot concentration distribution along z axis.

From figure 4 it can be seen that the soot particles are concentrated near the tunnel ceiling. This phenomenon occurs due to thermal buoyancy forces (natural convection). The thermal gradient causes the flow to flow towards the ceiling. Figure 5 shows the velocity in z axis.

Figure 5: Velocity field along Z axis of the gaseous mixture

As can be seen from Figure 5, there is a flow of the exhaust mixture upwards. The temperature distribution along z axis at t=300 sec and 3,000 sec is shown in figure 6.

Figure 6: The temperature distribution along z axis.

From figure 6 it can be seen that the temperature increases with z. The temperature decreases with time. The maximal temperature of the gaseous mixture at t=300 sec is 463ºC. The temperature of the gaseous mixture at t=3,000 sec is about 150ºC. This phenomenon occurs because two reasons:

  1. The gaseous mixture cools with time due to the radiation and convection to the tunnel walls
  2. The Flame was extinguished as a result of the oxygen consumption.

Figure 7 shows 3D plot of the temperature of the gaseous mixture at t=300 sec.

Figure 7: 3D plot of the temperature inside the tunnel.

From figure 7 it can be seen that the temperature inside the tunnel increases with z. The soot absorption coefficient as a function of z at t=300 sec and 3,000 sec is shown in figure 8.

Figure 8: The soot absorption coefficient distribution along z axis.

From figure 8 it can be seen that the soot absorption coefficient increases with z.  This is because the soot particles are concentrated near the ceiling (see figure 4).

6. Summary and Conclusions

This work describes a new radiation model applied in CFD calculations of pool tunnel fire scenario. This radiation code is implemented in the Fire Dynamics Simulator (FDS). The combustion is represented by means of the mixture fraction with a single step chemical reaction model. Large Eddy Simulation (LES) is used to model the dissipative processes. CFD results show that the extinction coefficient is strongly influenced by soot particle concentration field. A sensibility analysis has shown that the flame characteristics are strongly affected by the soot yield. It was found out that the soot concentration increases near the tunnel ceiling. This phenomenon occurs due to thermal buoyancy forces. The thermal gradient causes the flow to circulate. It was also found out that the temperature increases with the height. The temperature decreases with time. This phenomenon occurs because two reasons:

•  The gaseous mixture cools with time due to the radiation and convection to the tunnel walls

•The flame was extinguished because of the oxygen consumption.

 The model is described in detail in the following paper: https://www.researchgate.net/publication/313904486_CFD_Calculations_of_Soot_Radiation_Absorption_Coefficients_during_Pool_Tunnel_Fire

7. Further Reading

Tunnel Fire Dynamics – This book covers a wide range of issues in fire safety engineering in tunnels, describes the phenomena related to tunnel fire dynamics, presents state-of-the-art research, and gives detailed solutions to these major issues. Examples for calculations are provided. The aim is to significantly improve the understanding of fire safety engineering in tunnels. Chapters on fuel and ventilation control, combustion products, gas temperatures, heat fluxes, smoke stratification, visibility, tenability, design fire curves, heat release, fire suppression and detection, CFD modeling, and scaling techniques all equip readers to create their own fire safety plans for tunnels. This book should be purchased by any engineer or public official with responsibility for tunnels. It would also be of interest to many fire protection engineers as an application of evolving technical principles of fire safety. The following link contains more information about this book: https://www.springer.com/gp/book/9781493921980

The lectures dealing with turbulent combustion are shown in the following web link: https://allaboutcfd-tomersblog.com/2017/03/22/become-a-cfd-master-online-studying/

8. References

  1. Han, D. & Lee, B., Flame and smoke detection method for early real-time detection of a tunnel fire, Fire Safety Journal, 44:951-956, (2009).
  2. Alessandro G. Colombo, Nedies project: lessons learnt from tunnel accidents, in: JRC—ISIS EUR Report on March 2001.
  3. McGRATTAN, K. Fire Dynamics Simulator (Version 5) – Technical Reference Guide Volume 1: Mathematical Model, NIST Special Publication 1018, NIST, (2010).
  4. McGRATTAN, K., FORNEY, G.P., Fire Dynamics Simulator (Version 5) – User’s Guide. NIST Special Publication 1019, NIST, (2010).
  5. McGRATTAN, K., 2005, Numerical Simulation of the Caldecott Tunnel Fire, April 1982, NISTIR 7231.
  6. Eisner, H.S. & Smith, P.B. “Convection Effects from Underground Fires: the Backing of Smoke against the Ventilation” Research Report no. 96, Safety in Mines Research Establishment, (1954).
  7. D.M. Gates, R.F. Calfee, D.W. Hansen, and W.S. Benedict, “Line Parameters and Computed Spectra for Water Vapor Bands at 2.7 µm,” NBS monograph 71 (1964); R.F. Calfee and W.S. Benedict, “Carbon Dioxide spectral line Positions and Intensities Calculated for the 2.05 and 2.7 Micron Regions,” NBS Technical note 332, 1966.
  8. R.A. McClatchey, W.S. Benedict, S.A. Clough, D.E. Burch, K. Fox, L.S. Rothman, and J.S. Garing, “AFCRL Atmospheric Absorption Line Parameters Compilation”,  AFCRL Technical Report 0096, 1973.
  9. Laurence S. Rothman, John Schroeder and Kuilian Tang, Java HITRAN Atmospheric Workstation Manual, Atomic and Molecular Physics Division Harvard-Smithsonian Center for Astrophysics, 60 Garden St, Cambridge MA 02138-1516, April 2003.
  10. Eisner, H.S. & Smith, P.B. “Convection Effects from Underground Fires: the Backing of Smoke Against the Ventilation” Research Report no. 96 (1954). Safety in Mines Research Establishment.
  11. Sazhin, S.S., An Approximation for the Absorption Coefficient of Soot in a Radiating Gas, Fluent Europe L.

 